Last reviewed: 13 November 2026

Firefighting-foam stores can contain concentrates with very different environmental profiles. Some legacy foams contain regulated persistent substances, including certain PFAS compounds. Knowing exactly what is held on site is essential before deciding how to store, transfer or dispose of the concentrate or contaminated wash water.

Identify the foam and applicable restrictions

Check product records, safety data sheets, purchasing history and any PFAS or persistent organic pollutant information. Do not assume that a label reading “fluorine-free” establishes suitability for every application, and do not assume all fluorinated foams are subject to identical restrictions. The position depends on the substance, use, jurisdiction and applicable dates.

Maintain a clear inventory of affected products, particularly where foam is being replaced or equipment decontaminated. Seek specialist environmental and legal advice where waste classification or restricted substances are uncertain.

Keep concentrate and contaminated water contained

Inspect tanks, pumps, transfer lines and drum stores. Design secondary containment to prevent releases to soil and drainage. Suitable drip trays can catch small compatible drips, while drain covers may help protect a gully from a safe, manageable incident. Neither is enough for a large foam-concentrate tank failure.

Avoid washing a spill or flushing contaminated foam equipment into the drainage system. Firefighting-foam residues and wash water may need controlled collection, analysis, storage and specialist disposal. Check requirements before deciding whether any waste can leave the site.

Choose the response and disposal route

  • Isolate the source where safe and prevent entry to watercourses.
  • Use spill kits only for suitable minor identified releases.
  • Segregate contaminated materials pending proper classification.
  • Record losses, affected drains and recovery volumes.
  • Review the relevant regulator’s instructions before moving legacy stock.

For England, the Environment Agency’s September 2026 position statement on certain waste PFOA-containing firefighting foams (RPS 376) is a relevant reference, but it is conditional and does not remove other legal duties. Also see GOV.UK hazardous-waste guidance.